How often should fire alarms be tested and serviced?

Weekly manual call point tests, monthly checks, and six-monthly full service visits by a competent engineer, all logged in your fire alarm logbook.

One Check Services

Norfolk · Suffolk · Cambridgeshire

Back to resources

BS 5839-1 sets out the routine for commercial fire detection and alarm systems. The recommended minimum is:

  • Weekly: test a different manual call point each week to confirm the panel and alarm sounders work.
  • Monthly: visual check of standby batteries and a walk-round of all call points and detectors for damage or obstruction.
  • Six-monthly: full service visit by a competent service engineer, including detector, call point, sounder and panel function tests.
  • Annually: cause and effect validation where the system interfaces with other systems, plus a full discharge test of standby batteries.

Every test and visit must be recorded in a fire alarm logbook, kept on site, with any defects noted and rectified. Insurers and the enforcing authority will ask to see this record.

Higher-risk premises, or systems in harsh environments, may need more frequent visits. We set service intervals around the grade and risk of the system rather than a generic calendar.

Related questions

Quick answers to follow-ups.

Do I need to test every call point every week?

No. BS 5839-1 asks for a different call point each week, on rotation, so every point is tested over a period. The full set is exercised at the six-monthly service.

What if the system is monitored?

Monitored systems need an additional ARC signalling test, typically quarterly, to confirm the signal reaches the alarm receiving centre. We include this in planned maintenance contracts.