BS 5266-1 and BS EN 50172 set illuminance and duration on every escape route. Monthly flick tests and a full three-hour annual discharge are the minimum.

One Check Services

Norfolk · Suffolk · Cambridgeshire

Back to resources

Emergency lighting must let people see their way out safely if the normal supply fails. BS 5266-1 covers design and installation, and BS EN 50172 covers the routine. The minimum routine is:

  • Monthly: a short flick test, checking every fitting lights and that the 'healthy' indicator shows.
  • Annually: a full three-hour discharge test, with the normal supply isolated, confirming every fitting stays lit for the duration.
  • All tests logged, with defective units identified and rectified.

Illuminance on escape routes is typically 1 lux at floor level on the centre line, with 0.5 lux on the wider band. Duration is normally three hours for most commercial premises, though some lower-risk premises can use one-hour systems where occupants can leave quickly.

We design, install and maintain emergency lighting to the standard, and provide the test records that satisfy insurers and enforcing authorities.

Related questions

Quick answers to follow-ups.

Can I use self-test fittings to avoid monthly checks?

Self-test fittings reduce the manual workload but you still need to keep records and confirm any flagged faults are rectified. They are useful, not a substitute for a documented routine.

Do I need emergency lighting in a small office?

If the premises are open to the public, or staff could be present after dark, yes. Even a simple office needs escape lighting on the routes people would use to leave if the power failed.